FansRelated
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 0.0" SP | |||||||
|---|---|---|---|---|---|---|---|
| Catalog No. |
Prop. Dia. |
Drive Type |
Motor HP |
Prop RPM |
Max. BHP |
CFM | CFM Watt |
| AT10AP, SP AT15AP |
9" 14" |
Direct Direct |
1/6 1/8 |
3,150 1,660 |
0.16 0.11 |
1,090 1,660 |
5.1 10.9 |
| AT14F, G AT16F, G |
14" 16" |
Direct Direct |
1/8 1/4 |
1,660 1,650 |
0.12 0.22 |
1,880 2,940 |
15.9 16.7 |
| AT18F, G AT24F, G |
18" 24" |
Direct Direct |
1/3 1/3 |
1,660 1,060 |
0.38 0.39 |
4,270 6,050 |
11.4 16.4 |
Panel Fans
Pipe Fans
Aerotech's exhaust fans improve circulation. The ClassicTM panel fans can be installed in wall housings and customized with a discharge cone or fan hood to remove hot air from your building. The FPT is also an option for exhausting from the pit.
Install a discharge cone and boost airflow 10-17% with no additional electricity costs. Aerotech cones and hoods include snap-out safety guards for easy installation and maintenance. The construction of the accessories gives outstanding durability and reliability.
| 0.0" SP | 0.05" SP | 0.10" SP | 0.15" SP | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Catalog No. |
Prop. Dia. |
Drive Type |
Motor HP |
Prop RPM |
Max. BHP |
CFM | CFM Watt | CFM | CFM Watt | CFM | CFM Watt | CFM | CFM Watt |
| AT14F, G AT16F, G |
14" 16" |
Direct Direct |
1/8 1/4 |
1,660 1,650 |
0.14 0.24 |
2,140 3,440 |
14.7 13.6 |
2,010 3,150 |
13.1 12.2 |
1,890 2,940 |
11.9 11.0 |
1,690 2,690 |
10.1 10.1 |
| AT18F, G AT24F, G |
18" 24" |
Direct Direct |
1/3 1/3 |
1,660 1,060 |
0.43 0.39 |
4,550 6,510 |
10.9 15.8 |
4,380 6,140 |
10.1 14.4 |
4,230 5,700 |
9.7 12.9 |
4,070 5,290 |
8.9 11.9 |
| Catalog No. |
0.02" SP | 0.05" SP | ||
|---|---|---|---|---|
| RPM | CFM | RPM | CFM | |
| AT10AP, SP AT15AP AT14F, G AT16F, G AT18F, G AT24F, G |
700 550 550 500 500 500 |
125 160 140 340 530 870 |
700 600 600 600 600 600 |
50 100 85 260 430 870 |
Notes:
1) Performance shown is for installation type A: Free inlet, Free outlet.
2) Speed (RPM) shown is nominal. Performance is based on actual test speed.
3) CFM/Watt values shown are based on actual Watt input measurements with single-phase motors.
4) Fan airflow performance with fan hood, guard and shutter is 10-15% less than fan with discharge cone, guard and shutter.
Copyright © 1998-2013 U.S. Global Resources (USGR). All rights reserved.
Contact USGR :: Top
Web site developed by Infothai CM Co., Ltd.